Most Growatt error codes mean the inverter is protecting itself, not that it's broken. First, check how many digits the code has. Two-digit codes (01, 04, 07, 56…) come from Growatt's SPF off-grid inverters, the ones many Leyte and Biliran homes use for brownout backup. Three-digit codes ("Error 302", "Error 409") come from the MIN grid-tie and SPH hybrid inverters. The ones people search for most:
- SPF 04: battery voltage too low. Usually just a flat battery after a long brownout. Cut the load and let it recharge.
- SPF 07: overload timed out. Too many appliances at once. Switch some off.
- SPF 56: battery connection open, from a loose cable or blown fuse. Electrician.
- SPF 08, 09, 53, 57: internal faults. Restart once, then the repair centre.
- MIN/SPH Error 302: "No AC connection". Normal during a brownout, since grid-tie solar has to stop.
- MIN Error 409: bus over-voltage. Restart once, then call Growatt.
Last checked 12 November 2026, against Growatt's SPF 3500/5000 ES manual (v4.0), SPF 6000 ES Plus manual (EN 202212), MIN 2.5–6K TL-XH2 manual and SPH 3000–6000TL BL-UP manual (EN 202512). Code lists differ between model families, so match the code to the manual for your exact model.
First, safety
An SPF inverter brings solar DC, battery DC and grid or generator AC together in one box. Growatt's SPF safety instructions say:
- Don't open it. "Do not disassemble the unit. Take it to a qualified service center when service or repair is required."
- Switching it off isn't enough. "Disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk."
- Watch metal tools near batteries. A dropped tool can "spark or short circuit batteries… and could cause an explosion."
So below, "you" means no tools and no cables. You can read the screen, switch loads off, clear space around the unit, let the battery recharge and do one restart. Anything on the battery or DC side (cables, fuses, battery settings, panel strings) or the AC wiring is a job for a licensed electrician or your installer.
Which Growatt do you have? Read the code first
What you see | Inverter family | Examples sold in PH | Where the list comes from |
|---|---|---|---|
Two-digit number with the fault icon, red LED solid, buzzer continuous | SPF off-grid (fault) | SPF 6000 ES Plus | SPF manual "Fault Reference Code" |
Two-digit number flashing, red LED flashing, beeps once a second | SPF off-grid (warning, unit keeps running) | SPF 6000 ES Plus | SPF manual "Warning Indicator" |
"Error 3xx / 4xx" on the small screen | MIN grid-tie | MIN TL-X / TL-XH | MIN manual, section 11 |
"Error 5xx / 6xx" plus battery messages | SPH hybrid | SPH 5000TL BL-UP | SPH manual, section 9.2 |
Sungrid Energy's Growatt page currently lists the SPF 6000 ES Plus off-grid inverter and the SPH 5000TL BL-UP hybrid, among others. Take a photo of the screen before you press anything. The code, the time and what was running are what an installer will ask for. If you're still deciding on a brand, our LuxPower vs Growatt vs Deye comparison covers warranty and backup output.
Growatt SPF fault codes (01–81)
The SPF 3500/5000 ES and SPF 6000 ES Plus manuals list the same 21 fault codes. On a fault, output stops: the fault icon shows, the red LED stays on and the buzzer beeps continuously. "What Growatt says" comes from the manual's troubleshooting table. The "Who acts" column is our advice.
Code | Growatt's meaning | What Growatt says | Who acts |
|---|---|---|---|
01 | Fan is locked | Check all fans are working; replace the fan | Installer |
02 | Over temperature | Internal temperature over 100 °C. Check airflow isn't blocked and the room isn't too hot; check the thermistor plug | You first (airflow), then installer |
03 | Battery voltage too high | Battery over-charged. Check the battery spec and number of batteries | Installer |
04 | Battery voltage too low | Measure battery voltage; check SOC on a lithium battery; recharge the battery | You first (let it recharge), then electrician |
05 | Output short circuited | Check wiring and remove the abnormal load | Electrician |
06 / 58 | Output voltage too high / too low | Output above 280 Vac or below 80 Vac. Reduce the load, restart once | You (load), then repair centre |
07 | Overload time out | Overloaded above 110% for too long. Switch off some equipment | You |
08 | Bus voltage too high | With a lithium battery without BMS communication, check programs 19 and 21 aren't set too high; restart once | Installer |
09 / 53 / 57 | Bus soft start failed / inverter soft start failed / current sensor failed | "Internal components failed": restart once, then return to repair centre | Repair centre |
51 | Over current or surge | Restart once, then repair centre | You (restart), then repair centre |
52 | Bus voltage too low | Restart once, then repair centre | Repair centre if it repeats |
55 | Over DC voltage in AC output | Listed as "output voltage is unbalanced" in troubleshooting | Installer |
56 | Battery connection is open | Battery not connected well or fuse burnt. If wiring is fine, restart; if it repeats, repair centre | Electrician (DC side) |
60 | Negative power fault | Parallel systems: check AC output isn't wired to grid input, program 8, current-sharing cables, neutrals | Installer |
61 | PV voltage is too high | No fix listed. Panel string over the inverter's limit | Installer, urgently |
62 | Internal communication error | No fix listed | Repair centre |
80 / 81 | CAN fault / host loss | Parallel systems: check parallel cables and program 23 | Installer |
Two quick notes. Fault 61 is about panel wiring: the SPF 5000 ES accepts at most 450 V open-circuit from the panels and the SPF 6000 ES Plus 500 V, so an over-voltage string needs rewiring, not a restart. Our multimeter guide explains how Voc is measured. Faults 08 and 56 often come back to battery setup, so read the next section too.
Growatt SPF warning codes (the unit keeps running)
Warnings flash on the screen, the red LED flashes and the buzzer usually beeps once a second. The inverter keeps working, but something needs attention.
Code | Growatt's meaning | What it usually means at home |
|---|---|---|
01 | Fan locked while inverter is on | Fan blocked or failing; installer |
02 | Over temperature | Hot room, blocked vents |
03 | Battery over-charged | Charge settings; installer |
04 | Low battery | Battery getting flat; cut loads now, before fault 04 |
07 | Overload | Too much load; beeps every 0.5 s |
10 | Output power derating | Inverter limiting itself, often from heat |
12 | Solar charger stops due to low battery | Battery too flat for the solar charger |
13 | Solar charger stops due to high PV voltage | Panel voltage too high; installer |
14 | Solar charger stops due to overload | Charger at its limit |
15–17, 22, 25 | Parallel system warnings | Only on two or more inverters in parallel; installer |
18 | Buck over current | Installer if it repeats |
19 | Battery disconnect | Battery not seen (no beep); check the battery breaker is on, then electrician |
20 | BMS communication error | Lithium battery not talking to the inverter: cable or protocol setting |
21 | PV power insufficient | Cloudy, shaded or dirty panels, or early/late in the day |
33 | BMS communication loss | Same as 20 |
34–45 | Battery BMS warnings (cell over/under voltage, over/under temperature, MOSFET over temperature, system shut down) | The battery itself is protecting; check the battery's own manual |
For warning 20, Growatt's troubleshooting table gives two checks: the communication cable between inverter and battery, and whether the BMS protocol type is set correctly. On an SPF, Program 05 must be set to "LI" before Program 36 (protocol) appears. If a lithium battery has no communication cable, the manual says to use "User-Defined 2" in Program 05 instead. These are installer settings. Our battery not charging guide covers the battery side.
Why fault 04 hits after a long brownout
Fault 04 is the code people search for most, and in Biliran and Leyte it usually turns up at night after a long brownout. For lead-acid batteries, Growatt sets the SPF 5000 ES warning and cut-off voltages by load. The heavier the load, the lower the voltage it lets the battery fall to before stopping:
Load on the inverter | Low DC warning (warning 04) | Warning clears at | Low DC cut-off (fault 04) |
|---|---|---|---|
Under 20% | 44.0 V | 46.0 V | 42.0 V |
20% to under 50% | 42.8 V | 44.8 V | 40.8 V |
50% or more | 40.4 V | 42.4 V | 38.4 V |

In lithium mode the SPF 5000 ES works by state of charge instead: cut-off at 20% SOC by default (settable 5–50%), warning at cut-off + 5%, and it needs 30% SOC (cut-off + 10%) to cold-start from the battery. In lead-acid mode the cold-start voltage is 46.0 V. That's why an inverter that shut down on fault 04 often won't come back on battery alone. It needs sun or grid to recharge first. If yours won't power on at all, our inverter not turning on guide goes through the checks.
Worked example A: a fault 04 night in Naval (Solar Leyte illustration)
A home in Naval has an SPF 5000 ES with a 48 V AGM battery bank. During a 7 pm brownout it runs a ref, fans, lights and the TV, about 1,500 W. That's 1,500 ÷ 5,000 = 30% load, so the "20% to under 50%" row applies.
- When the battery falls to 42.8 V, warning 04 flashes and the unit beeps once a second. This is your cue to switch off everything except the ref.
- If nothing changes, at 40.8 V the inverter shows fault 04 and cuts the output.
- When the grid comes back, the SPF charges the battery from the grid again. If the brownout is still on, it waits for the sun. On battery alone it won't restart until the bank is back above 46.0 V.
If fault 04 keeps coming back on short brownouts even after a full sunny day, the battery may have lost capacity. Have an electrician test it.
Fault 07 and the aircon problem
The SPF 5000 ES is rated 5,000 W. Growatt's overload protection allows 10 seconds at 110–150% load and 5 seconds at 150% or more, with a surge capacity of twice the rated power for 5 seconds. After that it shows fault 07.
Worked example B: aircon plus water pump (Solar Leyte illustration)
Load | Share of 5,000 W | What the SPF does (per Growatt's spec) |
|---|---|---|
4,800 W | 96% | Runs normally |
6,000 W | 120% | Warning 07, then fault 07 after 10 seconds |
8,000 W | 160% | Fault 07 after 5 seconds |
5,000 × 110% = 5,500 W and 5,000 × 150% = 7,500 W are our calculations. The fix is simple: don't start the aircon, the water pump and the flat iron at the same time on battery. Program 06 sets whether the unit restarts by itself after an overload (default: disabled). Our solar for aircon guide explains what an aircon really draws.
"Mains exist but the unit works in battery mode"
This one confuses a lot of SPF owners in towns where evening voltage sags. Program 03 sets which AC input voltages the SPF will accept:
- Appliance (default): 90–280 Vac
- UPS: 170–280 Vac
- Generator: 90–280 Vac (Growatt says the generator should be at least 10 kVA)
If Program 03 is set to UPS and your evening voltage dips below 170 V, the SPF stays on battery even though the lights in the house next door are on. Growatt's troubleshooting table says to check whether the AC wires are too thin or too long, whether the generator is working well, and "if input voltage range setting is correct (UPS→Appliance)". It lists one more cause with the same flashing green LED: Program 01 (output priority) set to solar or battery first. Growatt's fix there is to change the output priority to "Utility first" if you want the grid to carry the load. Our AVR guide explains what low voltage does to other appliances.
Growatt MIN and SPH error codes (three digits)
Grid-tie (MIN) and hybrid (SPH) inverters use three-digit codes. Growatt splits them into system faults, which are usually caused by something outside the inverter, and inverter faults.
Code | Model family | Growatt's meaning | What Growatt says | Who acts |
|---|---|---|---|---|
Error 201 | MIN | Residual current (leakage) too high | Restart; if it persists, contact Growatt | Installer |
Error 202 | MIN, SPH | PV voltage high | Disconnect the DC switch immediately, check each string's voltage | Installer, urgently |
Error 203 | MIN, SPH | PV insulation resistance low | Check panel frame and inverter grounding, wet DC breaker, PV-to-ground impedance | Electrician |
Error 300 | MIN, SPH | AC voltage out of range | Check grid voltage and AC wiring, especially neutral and ground | You (wait), then electrician |
Error 302 | MIN, SPH | No AC connection | Check AC wiring and the AC breaker | You: check for a brownout first |
Error 303 | MIN | PE abnormal (neutral-to-earth over 30 V) | Check N and PE voltage and AC wiring | Electrician |
Error 304 | MIN, SPH | AC frequency out of range | Restart; check AC wiring | You (wait), then installer |
Error 402 | MIN, SPH | Output high DCI | Restart; contact Growatt if it persists | Installer |
Error 404 / 405 | MIN | Bus sample fault / relay fault | Restart; contact Growatt if it persists | Installer |
Error 407 | MIN | Auto test failure | Restart and repeat the auto test | Installer |
Error 408 | MIN | Over-temperature | Wait until the inverter's surroundings are below 60 °C, then restart | You (shade, airflow) |
Error 409 | MIN | Bus over-voltage | Restart; contact Growatt if it persists | Installer |
Error 411 / 414 / 417 | MIN | DSP–M3 communication, EEPROM, data mismatch | Restart; firmware update or board replacement | Installer / Growatt |
Error 420 | MIN | GFCI fault | Restart; contact Growatt if it persists | Electrician |
Error 500 | SPH | BMS COM fault | Check the battery communication port | Installer |
Error 502 / 503 | SPH | Battery voltage low / high | Check battery voltage | You (recharge), then installer |
Error 505 / 506 | SPH | Battery reversed / battery open | Check battery terminals | Electrician (DC side) |
Error 600 / 604 / 607 | SPH | Output short / EPS volt low / EPS overload | Restart; for EPS volt low, check and reduce the load on the backup (EPS) port | You (load), then electrician |
The MIN manual also lists warnings that leave the inverter running: Warning 203 (PV1 or PV2 short circuit: check panel polarity), 205 (PV boost failure), 401 (inverter can't talk to the export meter: check the meter is on and connected), 404 (EEPROM) and 405 (inconsistent firmware). Some numbers, like 203 and 404, appear as both an "Error" and a "Warning" with different meanings, so read the word in front of the number.
Worked example C: Error 302 during a BILECO brownout (Solar Leyte illustration)
At 2 pm the power goes out in Naval. The MIN grid-tie inverter on the roof stops and its screen says Error 302, No AC connection, even though it's sunny. That's expected. A grid-tie inverter without a battery must stop when the grid goes down. This "anti-islanding" protects linemen working on the lines (Meralco's net-metering FAQ, question 19). When the line comes back, the inverter reconnects by itself. Only call someone if Error 302 stays on while the grid is up and your AC breaker for the inverter is on.
Error 300 is the cousin. The MIN TL-XH2 accepts grid voltage of 160–276 V, so a deep evening sag or a surge can trip it even with the power on. If it happens daily, ask BILECO or your LEYECO to check your supply voltage. Our brownout vs blackout guide explains the voltage limits.
When to call someone, and what to send them
Growatt's MIN manual lists what support will ask for: serial number, model, the error message, a short description, grid voltage, DC input voltage, whether you can reproduce it, whether it happened before, the conditions at the time, and your panel details (model, watts, Voc, Vmp, Imp, panels per string). Have those ready and you'll save a site visit.
- You can handle: SPF 04 and warning 04 (recharge, cut loads), 07 (overload), 02 and Error 408 (heat and airflow), warning 21 (low sun), Error 302 during a real brownout.
- Electrician or installer: 03, 05, 08, 56, 61, warnings 19, 20 and 33, Errors 201, 202, 203, 303, 420, 500–506.
- Repair centre or Growatt: 09, 53, 57, 62, and anything that comes back after one restart.
Growatt's own contact page lists offices in places like Thailand, Vietnam and Australia but none in the Philippines, plus a global service email (service@growatt.com). In practice, warranty claims go through the shop or installer that sold you the unit, so keep the receipt and serial number. If the inverter is out of warranty and you're thinking of replacing it, you can request a quote and compare.

FAQ
What does error 04 mean on a Growatt inverter?
On an SPF off-grid inverter, it means the battery voltage is too low. As a warning (flashing), it's telling you to cut loads now. As a fault, output has stopped. Growatt says to measure the battery voltage, check the SOC on lithium, and recharge.
How do I reset a Growatt SPF fault?
Growatt's note says that to restart, disconnect all power sources and wait until the LCD goes off, then boot from the battery only. Do it once. If the same fault comes back, especially 08, 09, 53, 56 or 57, stop and call an electrician or the repair centre.
Ano ang Error 302 sa Growatt?
"No AC connection." Ibig sabihin, walang kuryente galing sa grid, kaya normal ito kapag may brownout. Babalik ang inverter kapag bumalik na ang kuryente. Kung may kuryente pero Error 302 pa rin, ipa-check ang AC breaker at wiring sa electrician.
Is Growatt error 409 serious?
On a MIN inverter, 409 is "bus over-voltage", an inverter fault. Growatt says restart it, and if the problem continues, contact Growatt. It isn't something to fix at home.
Solar Leyte is run by MACC Systems & Energy Solutions Inc., a solar installer in Naval, Biliran.
Get a free solar quote from MACC
Planning a hybrid or off-grid system for brownouts? Send us a recent BILECO or LEYECO bill and we'll get back to you with a free, no-obligation written quote.
- Call/Text: 0955 723 5093
- Email: official@macc-inc.com
- Website: www.macc-inc.com
- Or use the site quote form: /quote
Related guides
- Grid-tie vs hybrid vs off-grid solar: which works in a brownout?
- Deye hybrid inverter error codes
- MUST and Axpert inverter error codes
- 12V vs 24V vs 48V solar systems
Sources (all checked 12 November 2026)
- Growatt SPF 3500/5000 ES user manual, version 4.0 (PDF): safety instructions p. 3; LCD settings (programs 01, 02, 03, 05, 06, 12, 13, 19–21, 23) pp. 17–20; lithium BMS set-up (Program 05 "LI", then Program 36) pp. 8–9; Fault Reference Code p. 35 (21 faults); Warning Indicator pp. 35–36; Table 2 (5 kW rating, overload protection 5 s at ≥150% / 10 s at 110–150%, surge 2× for 5 s, cold start 46.0 V / 30% SOC, low DC warning and cut-off voltages by load, Li cut-off 20% SOC) p. 39; MPPT 450 V max Voc p. 40; Trouble Shooting pp. 41–42 (PDF page numbers).
- Growatt SPF 6000 ES Plus user manual, EN 202212 (PDF): same fault list p. 37 and warning list p. 38; 6 kW rating and battery specs pp. 40–41; max PV open-circuit voltage 500 V pp. 14 and 42; Trouble Shooting pp. 43–44. The same file is linked from Growatt's SPF 6000 ES Plus product page.
- Growatt MIN 2.5–6K TL-XH2 user manual (PDF): what to tell support (section 11.1), system faults and warnings (section 11.2/11.3, PDF p. 51), inverter faults 402–420 (section 11.4, PDF p. 53), AC voltage range 160–276 V (specifications, PDF p. 55). Linked from Growatt's MIN 2500–6000 TL-XH2 product page.
- Growatt SPH 3000–6000TL BL-UP user manual, EN 202512 (PDF): system fault list and suggestions (section 9.2, PDF pp. 63–64).
- Sungrid Energy, Growatt inverters: Philippine seller page listing the SPF 6000 ES Plus, SPH 5000TL BL-UP and other Growatt models.
- Growatt contact page: office list (no Philippine office) and service@growatt.com.
- Meralco, Solar and Net-Metering FAQ: question 19 (systems without a battery stop supplying power during an outage).
- Worked examples A–C: Solar Leyte illustrations built from the Growatt figures above, not real cases. Percentages and wattages (1,500 ÷ 5,000 = 30%; 5,000 × 110% = 5,500 W; 5,000 × 150% = 7,500 W) are our calculations.